This will make the job of insulating the pipe much easier.
Insulate fire sprinkler pipes in the attic.
Insulate unconditioned areas where sprinkler pipes travel to keep the space as warm as possible during freezing weather.
With no flow through the sprinkler piping under normal conditions insulating the piping in this manner can lead to freezing and subsequent water discharge from ruptured piping.
Back to back v bb single directional v sd and attic upright models available in 5 6 and 8 0 k factors to protect various roof pitches.
When sprinkler pipe is run in an attic certain precautions must be taken.
If your fire sprinkler pipes are exposed to cold exterior temperatures they are more likely to freeze.
A 8 16 4 1 6 wet pipe systems covered by 8 16 4 1 6 have water filled pipes up to the sprinklers.
Most sprinklers are wet pipe systems meaning they contain water at all times.
Insulation shall follow the guidelines of the insulation manufacturer.
All too often insulators accustomed to dealing with plumbing and heating systems wrap the sprinkler piping in insulation insulating it from the warm building envelope as well as the attic cold.
In attics piping should be as close to the ceiling as possible with insulation placed over the sprinkler pipe.
As much as possible the sprinkler contractor should try to run pipe in a single stud or joist space.
Compared to standard spray sprinklers viking s new attic sprinkler system requires fewer sprinklers and branch lines to protect most attic spaces providing significant material and labor savings.
When foam cannot be used other insulative material takes its place.
A wet pipe system shall be permitted to be installed in unheated attic spaces in areas subject to freezing where sprinkler piping is completely covered with insulation.
Pipe run horizontally should be covered by two layers of insulation.
If you can safely inspect your sprinkler pipes in the attic and you can see exposed.